

GENERAL:
Provide
a complete Lightning Protection System as shown on the drawings
and as specified herein. This system shall be installed
by a firm actively engaged in the installation of Master
Labeled Lightning Protection Systems a minimum of five (5)
years and shall be listed by Underwriters Laboratories,
such as Maxwell Lightning Protection Company, 621 Pond Street,
Dayton, Ohio 45402, (937) 228-7250, or 1-800-872-1657.
The completed
system shall comply with the latest edition of the Installation
Requirements for Master Labeled Lightning Protection System
U.L. 96A, and the National Fire Protection Association must
be L.P.I. certified and in good standing and so certified.
MATERIALS:
All
materials used in this installation shall be labeled or
listed by Underwriters Laboratories, Inc. for use in Master
Labeled Lightning Protection Systems. The catalog numbers
referred to on the drawings and herein are those of EAST
COAST LIGHTNING PROTECTION, MAXWELL LIGHTNING PROTECTION
COMPANY or THOMPSON LIGHTNING PROTECTION.
AIR
TERMINALS:
Air
terminals shall project a minimum of ten (10) inches above
the objects protected and shall be located at intervals
not exceeding 20' 0" along ridges and around the perimeter
of flat roof or gently sloping roofs. Flat or gently sloping
roofs exceeding 50' 0" in width shall be provided with
additional air terminals at intervals not exceeding 50'
0" on the flat or gently sloping area. Air terminals
shall be located within 24 inches of the roof edge and outside
corners of the protected area.
Air terminals
shall be provided for metal stacks, flues and mechanical
equipment having a metal thickness of less than 3/16"
and not within a zone of protection of an air terminal.
Equipment with metal thickness 3/16" or greater shall
be bonded per code requirements.
Air terminals
shall be No. 71, ½" X 12" (or longer as required)
solid copper using air terminal bases of cast bronze construction.
CONDUCTORS:
Main
size conductors on the roof shall be No. 28, Class II copper
lightning conductor consisting of 28 strands of 14 AWG copper
wire weighing 375 lbs. per 1000 feet.
All secondary
bonding conductors shall be No. 14, secondary bonding conductor
consisting of 14 strands of 17 AWG copper wire.
All down
conductors shall be No. 28, Class II copper lightning conductor.
Down conductors shall be concealed in exterior wall construction.
Note:
Buildings over 60' require a conductor counterpoise cable
of 28/14 copper to meet N.F.P.A. code requirements for this
project.
ROOF
PENETRATION - FOR NEW CONSTRUCTION:
All
roof penetrations shall be made using a conduit sleeve passing
through a No. 227G pitch pocket. The pitch pocket shall
be installed by the roofing contractor. The roofing contractor
must include all additional expenses for this additional
work. Any roof pads, or roof stripping must be supplied
and installed by the roofing contractor, at the roofing
contractors expense, to maintain the roof warranty.
COMMON
GROUNDING & BONDING OF METAL BODIES:
Common
grounding of all mediums within the building shall be ensured
by connection to cold water piping or by direct bonding
using main size conductors and fittings.
Metal bodies
of conductance (metal bodies with a metal thickness of 3/16"
or greater and not located within the zone of protection
of an air terminal) shall be bonded using main size conductors
and fittings per code requirements.
Metal bodies
of inductance (metal bodies located within 6' 0" of
the lightning protection system) shall be bonded to the
system using secondary bonding conductors and fittings unless
inherently bonded through construction to another bonded
metal body.
GROUND
ELECTRODES:
Ground
electrodes shall be No. 5810, 5/8" X 10' long copper
clad ground rods located as shown on the drawings. Down
conductors shall be connected to the ground rods using exothermic
weld connections.
STRUCTURAL
STEEL SYSTEM:
Structural
steel may be substituted for down conductors. Ground main
steel columns and average of 60' using Class II material.
Roof penetrations from steel to perimeter cables at 100',
per U.L. 96A, L.P.I. 175, and N.F.P.A. 780. Use exothermic
weld to all steel connections.
INSPECTION
AND ACCEPTANCE:
Upon completion
of the installation the contractor shall deliver to the
owner the Master Label issued by Underwriters Laboratories,
Inc. for this system. If the new addition connects to an
existing building that is not protected or brought up-to-date
a U.L. Letter of Findings must be obtained, at the lightning
protection contractors expense.
Note:
Surge Arresters at the main electrical panel are not included
under our scope of work. This item must be installed and
supplied by the Electrical Contractor.
SUBMITTALS:
Drawings shall
be submitted for approval before delivering material and
beginning work. Drawings to show number of points, size
locations, conductor routes and size, grounding and details
of connectors. Catalog data for all items or material used
shall be submitted.
Lightning
protection contractor shall submit his Underwriters Laboratories
listing number, along with a copy of ten successful U.L.
inspection certificates and their identification numbers
installed in the last five years. Contractor must show proof
of insurance and must be substance to be bonded.
|